littelfuse.com © 2014 Littelfuse POWR-GARD
®
Products
Rev: 020414
POWR-GARD
®
Fuse Datasheet
2 of 3
Electrical Specification – Agency Requirements
AMPERAGE RATING
OPENING TIME (MINUTES)
135% of Amp Rating per UL 200% of Amp Rating per UL
2.5-3.5 60 Max 4 Max
SPXI SERIES IN-LINE SOLAR FUSE
PERCENT OF UPRATING
PERCENT OF DOWNRATING
AMBIENT TEMPERATURE
60
40
20
0
0
20
40
60
-60˚ C -40˚ C -20˚ C 0˚ C 20˚ C 40˚ C 60˚ C 80˚ C 100˚ C 120˚ C 140˚ C
-76˚ F -40˚ F -4˚ F -32˚ F 68˚ F 104˚ F 140˚ F 176˚ F 212˚ F 248˚ F 284˚ F
Temperature Rerating Curve
(Temperature of Air Immediately Surrounding Fuse)
Ordering Information
SERIES AMPERAGE AMP CODE CATALOG NUMBER PRODUCT MARKING PACK QUANTITY ORDERING NUMBER UPC
SPXI 2.5 02.5 SPXI02.5 SPXI 2 ½
10 SPXI02.5T 07945880950
50 SPXI02.5L 07945880949
SPXI 3.5 03.5 SPXI03.5 SPXI 3 ½
10 SPXI03.5T 07945880808
50 SPXI03.5L 07945880149
Electrical Specifications
AMPERAGE
VOLTAGE
INTERRUPTING
RATING
WIRE RANGE
NOM COLD
RESISTANCE
(ohm)
WATTS LOSS
AT 100% RATED
CURRENT (W)
WATTS LOSS
AT 80% RATED
CURRENT (W)
WATTS LOSS
AT 70% RATED
CURRENT (W)
MELTING
I
2
t (A
2
s) 15 kA
(1500VDC)
TOTAL
CLEARING
I
2
t (A
2
s) 15 kA
(1500VDC)
AGENCY
APPROVALS
DC AC DC UL RECOGNIZED
2.5 1500 – 15 kA
10 AWG (6 mm
2
)
0.099 0.859 0.482 0.350 6.78 15.78 •
3.5 1500 – 15 kA
10 AWG (6 mm
2
)
0.0711 1.56 0.81 0.57 25 50 •
Kommentare zu diesen Handbüchern