Littelfuse MPS (PGR-6300) Series Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Hardware Littelfuse MPS (PGR-6300) Series herunter. Littelfuse MPS (PGR-6300) Series User Manual [en] [es] Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/mps
PHASE CT
PHASE CT
GF CT
PHASE CT
MPU-CIM
MPS-RTD
RTD x 8
L2
L1
MPU-32
M
(Current Input Module)
(Motor Protection Relay)
PHASE CT
PHASE CT
GF CT
PHASE CT
L2
MPS-CTU
L1
M
MPS-RTD
MPS-OPI
RTD x 8
(Control Unit)
(Temperature
Input Module)
(Temperature
Input Module)
(Operator Interface)
Motor Protection–Advanced
MPS SERIES (PGR-6300)
Motor Protection System
1
2
Description
The MPS Motor Protection System monitors voltage, current,
and temperature to provide a comprehensive package of
22 protective functions. The MPS is a modular system with
integrated protection, motor control, metering, and data-logging
functions. This system is typically used to provide protection for
three-phase low- and medium-voltage, medium-
to high-horsepower induction motors.
Operator Interface (MPS-OPI)
g
Large, bright, 4 x 20 vacuum-fluorescent display
g
Display metered values
g
Access set points
g
Powered by Control Unit
g
Panel mount or attach directly to Control Unit
g
Remote mounting (1.2 km or 4000 ft maximum loop length)
g
1/2 DIN size
g
Hazardous-location certified
Control Unit (MPS-CTU)
g
Current inputs—5-A or 1-A secondary phase current transformers
g
Voltage inputs—up to 600 V without PTs
g
Earth-leakage input—5-A or 1-A secondary or sensitive transformer
g
Tachometer (high-speed pulse) input
g
8 digital inputs, 5 relay outputs, 1 analog input and output
g
24-Vdc supply for OPI and RTD modules, and for digital inputs
g
IRIG-B time-code input
g
1/2 DIN size, surface mount
g
RS-485 network communications (Standard)
g
DeviceNet
, Profibus
®
, or Ethernet communications available
1
2
Phase Current Transformers
Phase CTs are required to detect phase
currents.
Ground-Fault Current Transformer
Required zero-sequence current transformer
detects ground-fault current. Available with 5-A
and 30-A primary ratings for low-level pickup.
MPS-RTD Temperature Input Module
Optional module provides 8 inputs to connect
Pt100, Ni100, Ni120, and Cu10 RTDs.
MPS-DIF Differential Current Module
Optional motor differential protection,
compatible with core balance and summation
current transformer connections.
B
C
Accessories
A
ACCESSORIES REQUIREMENT
MPS-OPI-01-00 Recommended
Phase CTs Required
Ground-Fault CT Recommended
MPS-RTD-01-00 Optional
MPS-DIF-01-00 Optional
SE-IP65CVR-M Optional
1
2
ORDERING NUMBER COMMUNICATIONS
MPS-CTU-01-00 RS-485
MPS-CTU-02-00 RS-485 & DeviceNet
MPS-CTU-03-00 RS-485 & Profibus
®
MPS-CTU-04-00
RS-485 & EtherNet/IP™ & Modbus
®
TCP
Ordering Information
Simplified Circuit Diagram
B
C
A
D
Rev: 4-A-050213
Based on Manual Rev 5
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - MPS SERIES (PGR-6300)

Protection Relays & Controls© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/mpsPHASE CTPHASE CTGF CTPHASE CTMPU-CIMMPS-RTDRTD x

Seite 2

Protection Relays & Controls© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/mpsMotor Protection–Advanced PHASEVOLTAGESMPS-CTUCON

Kommentare zu diesen Handbüchern

Keine Kommentare